electric control panel type Q2PT-CE, Q2PTD-CE with a microprocessor, with amperometric protection, to operate 2 triphase pressurized or drainage electropumps (with two different programm).
The microprocessor control panel type Q2PT-CE, Q2PTD-CE with amperometric protection has been designed in an easy and modern way to command and control, by means of a micro processor card, the working of two triphase pumps, either pressurization or drainage.
The control panel type Q2PT/CE50 –1000, Q2PTD-CE 50-1000 has been built to cover the whole range of electric pumps from 0.33KW to 7.5KW (three-phase). This allows us to have a single type of control panel, which can be used for all the different sizes of motor in commercial use. A pressure transducer, type TP1 and produced by us, is required in order to use the control panel with the characteristics described below.
This system solves the problem of setting the manometer and the two pressostats to command the respective pumps as
the reading of the pressure (shown on the display) and the command of the pumps takes place through the pressure
transducer fixed on the manifold.
DIME OF IMPLANTATION H= 190mm W= 130mm
CHARACTERISTICS OF OUR ELECTRIC CONTROL PANEL TYPE Q2PT-CE AND Q2PTD-CE
- Box in thermoplastic material IP
- Mother card with electronic parts
- Amperometric protection
- Micro processor electronic card with LCD with the possibility to show, if the pumps have been preset through the respective gear buttons, the voltage, electrical input from the motors.
Visualisation of the settings, for example min and max pressure, (min. max level) level pressure, cavitation pressure, waiting time to start pump2, time interval pump 2, settings of the input of the respective motors 1 and 2. Alarms: for example excessive electrical input in the motors 1 and 2, lack of water, errors in the data settings, minimun network voltage. - Tension feed 3~ 50/60 Hz ± 10%
- Entrance in low voltage (12V cc.)
- Exchange circuit of starting sequence for the motors, integrated on the electric card
- Circuit to control sequence or missing phases
- 1 led line, white
- 2 led march pumps, green
- Led generic alarms, red
- 2 gear buttons
- 2 stop buttons
- 2 selectors Ø 22 for automatic-off- manual working
- Fuses for the protection of the motors and auxiliary
- 2 contact breakers to control the engines
- General selector with lock door
- Entry and exit of the cables by means of anti tear cables
USE CONDITIONS
- Degree of protection : IP55
- Field of operation : -5°C + 40°C
- Relative humidity : 50% with temperature of 40°C
Electric control panel type Q2PT-CE and Q2PTD-CE models
CODE | CONTROL PANEL TYPE | MAX. POWER TO 230V. MONOPHASE | MAX. POWER TO 400V. MONOPHASE | MAX AMPEROMETRIC PROTECTION (ADJUSTABLE) | DIMENSIONS IN mm | WEIGHT | ||||
---|---|---|---|---|---|---|---|---|---|---|
KW | HP | KW | HP | A | H | W | D | Kg | ||
700235 | Q2PT/CE 50¸400 – Q2PTD/CE 50¸400 | 1.5 | 2 | 3 | 4 | 25A | 330 | 225 | 145 | 3.6 |
700240 | Q2PT/CE 550¸750 – Q2PTD/CE 550¸750 | 3.0 | 4 | 5.5 | 7.5 | 25A | 330 | 225 | 145 | 3.6 |
700245 | Q2PT/CE 1000 – Q2PTD/CE 1000 | 4.0 | 5.5 | 7.5 | 10 | 25A | 330 | 225 | 145 | 3.6 |